Description
The PDU330AT6L2130 8.6kW 3-Phase 208V ATS/Monitored PDU provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Working in tandem with a required 0U vertical outlet accessory(sold separately; choose from PDU3VD351, PDU3V20D354, PDU3V20D354A or PDU3V20D354B), the 1U PDU330AT6L2130 is ideal for data centers and server rooms.
Dual 6-foot input cords with L21-30P plugs connect to separate primary and secondary 3-phase power sources. The PDU constantly evaluates the power quality of both input sources. Dynamic solid-state(TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1-5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption.
Built-in Ethernet network interface allows remote access to the PDU for power monitoring, configuration, control and notifications via web browser, SSH, telnet or SNMP. Provides real-time load/current data with billing-grade accuracy(+/- 1 percent). Tiered access privileges allow both an administrator and a guest to log in. Automated alerts help prevent accidental overloads, power loss and downtime. Digital LED display indicates power availability, voltage, source A/B input status, output load and power factor, as well as temperature and humidity conditions with the optional ENVIROSENSE module(sold separately).
Dual 6-foot input cords with L21-30P plugs connect to separate primary and secondary 3-phase power sources. The PDU constantly evaluates the power quality of both input sources. Dynamic solid-state(TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1-5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption.
Built-in Ethernet network interface allows remote access to the PDU for power monitoring, configuration, control and notifications via web browser, SSH, telnet or SNMP. Provides real-time load/current data with billing-grade accuracy(+/- 1 percent). Tiered access privileges allow both an administrator and a guest to log in. Automated alerts help prevent accidental overloads, power loss and downtime. Digital LED display indicates power availability, voltage, source A/B input status, output load and power factor, as well as temperature and humidity conditions with the optional ENVIROSENSE module(sold separately).
- Ethernet network interface for remote access
- Digital LED display for real-time status monitoring
- Requires Tripp Lite 0U outlet accessory (sold separately)
- 3-phase L21-30P input and single-phase 208V output
- Automatic transfer switching within 1-5 ms
- Receptacle Type : IEC 60320 C19,IEC 60320 C13
- Environmentally Friendly : Yes
- PDU Type : Monitored
- Power Rating (Watt) : 8.60 kW
- Input Voltage : 230 V AC
- Product Series : Monitored
- Management :
- HTTP
- HTTPS
- PowerAlert
- SMTP
- SNMPv1
- SNMPv2
- SNMPv3
- Telnet
- SSH
- FTP
- DHCP
- BOOTP and NTP
- Limited Warranty : 2 Year
- Plug/Connector Detail : 2 x NEMA L21-30P
- Package Contents :
- PDU330AT6L2130 8.6kW 3-Phase 208V ATS/Monitored PDU
- Rack installation brackets
- Configuration cable
- Owner's manual
- Grounding Lug
- Plug/Connector Type : NEMA L21-30P
- Product Type : PDU
- Mount Type : Rack-mountable
- Protection Type : Overload Protection
- Manufacturer : Tripp Lite by Eaton
- Product Model : PDU330AT6L2130
- Output Voltage : 208 V AC
- Mounting Orientation : Horizontal
- Input Current : 24 A
- Rack Height : 1U/2U
- Country of Origin : China
- Manufacturer Website Address : https://tripplite.eaton.com/